Falling window leaves can be a considerable risk to life and limb of persons in the vicinity. Therefore, the use of GEZE safety scissors is mandatory when using GEZE drives on bottom-hung windows.
Powerchain
Space needed on frame (min.)
Frame installation inward-opening: 50/61 mm (for swing leaf DIN L), leaf installation inward-opening: 30/41 mm (for swing leaf DIN R), frame installation outward-opening: 50 mm
Space requirement on leaf (min.)
Frame installation inward-opening: 40 mm, leaf installation inward-opening: 50 mm Frame installation outward-opening 30/41 mm (for swing leaf DIN R)
Available stroke length
600 mm, 800 mm, 1200 mm
Opening speed RWA
15 mm/s
Opening speed ventilation
5 mm/s
Closing speed (max.)
5 mm/s
Force of pressure (max.)
600 N (depending on stroke), see force-path diagram
Holding force (max.)
3000 N
Tensile force
600 N
Leaf weight
200 kg*
Overlap range
0 - 23 mm (depending on application and brackets)
Voltage at operation
24 V ± 25 %
operating voltage
24 V DC
Current consumption
1.5 A
Current consumption according to area of application
Ventilation (24 V): 1.2 A; RWA (18 V): 1.5 A
Power consumption
36 W
Duty rating
30 %
Special length of power supply cable
5 m, 7.5 m
Min. core cross section
0.75 mm²
Number of cables
4 cores
Service temperature
-5 - 70 °C
IP rating
IP40
protection rating
III
Synchronising function
Yes
Adjustable opening speed (ventilation)
Yes
Additional locking available
Yes
Type of additional locking mechanism
Locking drive
Type of stroke shortening
Synchronising unit, Factory setting
End position cut-off extended
electronic, via internal path sensor
End position cut-off retracted
electronic via current consumption
Overload cut-off
Yes
Complete opening within 60 s
yes, up to 800 mm stroke, including locking drive
SHEV tested
Yes
SHEV additional information
yes, up to 800 mm stroke, including locking drive
Number synchronisation drive units
4
KNX ability
Yes
Bottom-hung window INWARD-opening frame installation
Yes
Bottom-hung window INWARD-opening leaf installation
Yes
Bottom-hung window OUTWARD-opening frame installation
Yes
Side-hung window INWARD-opening frame installation
Yes
Side-hung window INWARD-opening door leaf installation
Yes
Side-hung window OUTWARD-opening frame installation
Yes
Top-hung window INWARD-opening frame installation
Yes
Top-hung window INWARD-opening leaf installation
Yes
Top-hung window OUTWARD-opening frame installation
Yes
OUTWARD-opening roof window
Yes